EL3356 | BECKHOFF | EtherCAT Terminal, 1-channel Analog input, Measuring Bridge, Full Bridge, 16 Bit
₹ 23,750.00
EL3356 | BECKHOFF | EtherCAT Terminal, 1-channel Analog input, Measuring Bridge, Full Bridge, 16 Bit
está agotado y se enviará tan pronto como vuelva a estar disponible.
Warranty
We provide a 1-year warranty from the date of purchase for new products. Additionally, surplus / used items come with a 30-day warranty.
Delivery and Shipping
We aim to process orders within 5-7 business days. Shipping options vary by location with tracking provided; international shipping available with customs duties responsibility on customers.
EL3356 | BECKHOFF | EtherCAT Terminal, 1-channel Analog input, Measuring Bridge, Full Bridge, 16 Bit
EL3356 | BECKHOFF | EtherCAT Terminal, 1-channel Analog input, Meas...
EL3356 | BECKHOFF | EtherCAT Terminal, 1-channel Analog input, Measuring Bridge, Full Bridge, 16 Bit
está agotado y se enviará tan pronto como vuelva a estar disponible.
Manufacturer Part Number (MPN)
EL3356
Original Equipment Manufacturer
BECKHOFF
Descripción
Number of inputs
2, for 1 resistor bridge in full bridge technology
Power supply
via the E-bus
Distributed clocks
–
Measuring range UD
max. ±27 mV
Measuring range UREF
max. ±13.8 V
Internal resistance
> 200 kΩ (UREF), > 1 MΩ (UD)
Supported nominal sensitivity
all, parameter resolution: 0.01 µV/V; recommended: 0.5…4 mV/V
Input filter limit frequency
10 kHz low pass (-3 dB)
Conversion rate
100…4 samples/s (10…250 ms conversion time)
Power supply UV
up to 12 V DC from power contacts, dependent on sensor
Resolution
16 bit, 32 bit presentation
Measurement error/uncertainty
< ±0.01% for the calculated load value in relation to the final load value with a 12 V feed and 24 mV bridge voltage (hence nominal strain gauge characteristic value of 2 mV/V), self-calibration active, 50 Hz filter active
EL3356 | BECKHOFF | EtherCAT Terminal, 1-channel Analog input, Measuring Bridge, Full Bridge, 16 Bit
Precio normal₹ 23,750.00
Precio unitario
Agotado
Number of inputs
2, for 1 resistor bridge in full bridge technology
Power supply
via the E-bus
Distributed clocks
–
Measuring range UD
max. ±27 mV
Measuring range UREF
max. ±13.8 V
Internal resistance
> 200 kΩ (UREF), > 1 MΩ (UD)
Supported nominal sensitivity
all, parameter resolution: 0.01 µV/V; recommended: 0.5…4 mV/V
Input filter limit frequency
10 kHz low pass (-3 dB)
Conversion rate
100…4 samples/s (10…250 ms conversion time)
Power supply UV
up to 12 V DC from power contacts, dependent on sensor
Resolution
16 bit, 32 bit presentation
Measurement error/uncertainty
< ±0.01% for the calculated load value in relation to the final load value with a 12 V feed and 24 mV bridge voltage (hence nominal strain gauge characteristic value of 2 mV/V), self-calibration active, 50 Hz filter active