1083731 | SICK SENSORS | PAC50-DNA Pressure Sensor

₹ 17,438.40

Get Best Price on WhatsApp

Product Description

Medium Dry compressed air
Pressure type Gauge pressure
Pressure unit bar
Measuring range 0 bar ... 10 bar
Overpressure safety 15 bar
Process temperature 0 °C ... +60 °C
Maximum ohmic load RA Optional, 4 mA ... 20 mA / 0 V… 10 V. Automatic detection depending on connected load or programmable. Output signals can be inverted: 20 mA ... 4 mA / 10 V ... 0 V, Load resistance for current output < 600 Ohm, Load resistance with current output > 3 kOhm
Process connection ¼" NPT female 1)
Housing material Housing: polycarbonate, Buttons: TPE, DIN rail mounting: POM, seals: NBR
Connection type M12 round connector x 1, 4-pin
Supply voltage 17 V DC ... 30 V DC
Power consumption Max. 40 mA at L+ = 24 VDC

 

Warranty

We provide a 1-year warranty from the date of purchase for new products. Additionally, surplus / used items come with a 30-day warranty.

Delivery and Shipping

We aim to process orders within 5-7 business days. Shipping options vary by location with tracking provided; international shipping available with customs duties responsibility on customers.


SPARECRUX is NOT an authorized distributor for SICK SENSORS

Manufacturer Part Number (MPN)

1083731

Original Equipment Manufacturer

SICK SENSORS

PDF Product Datasheet
  • 100% Tested & Verified Products

  • GST Invoice Available

  • Warranty Included

  • Trusted by 5000+ Industrial Buyers

Medium - Dry compressed air

Pressure Type - Gauge pressure

Pressure Unit - bar

Measuring Range - 0 bar to 10 bar

Overpressure Safety - 15 bar

Process Temperature - 0 °C to +60 °C

Maximum Ohmic Load (RA) - Optional, 4–20 mA / 0–10 V. Automatic detection depending on connected load or programmable. Output signals can be inverted: 20–4 mA / 10–0 V. Load resistance for current output: < 600 Ω. Load resistance for voltage output: > 3 kΩ.

Zero Point Adjustment - Maximum ±5% of span

Output Signal - 2 × PNP / NPN / Push-Pull

Diagnostics Output - Switching output 2 can be set as diagnostics output

Communication Interface - -

Process Connection - ¼" NPT female

Housing Material - Housing: Polycarbonate; Buttons: TPE; DIN rail mounting: POM; Seals: NBR

Connection Type - M12 round connector × 1, 4-pin

Supply Voltage - 17 V DC to 30 V DC

Power Consumption - Maximum 40 mA at L+ = 24 V DC

Electrical Safety - Protection Class III; Overvoltage Protection: 32 V DC; Short-circuit Protection: QA, Q1, Q2 towards M and L+; Reverse Polarity Protection: L+ to M

CE Conformity - EMC Directive: 2004/108/EC, EN 61326-2-3

Not applicable for this product

Weight (Sensor) - Approx. 40 g

EU Declaration of Conformity - ✔

UK Declaration of Conformity - ✔

ACMA Declaration of Conformity - ✔

China RoHS - ✔

China Compulsory Product Certification (CCC) Exempt - ✔

ECLASS 5.1.4 - 27200620

ECLASS 6.0 - 27200620

ECLASS 7.0 - 27200620

ECLASS 8.0 - 27200620