Specification Details
Operating Voltage (UB) 24V DC (minimum 18V, maximum 30V)
Rated Current (IN) 2 A per channel
Number of Channels 2
Voltage Drop at IN Typically 180 mV per channel
Overload Disconnection (IOL) - 1.05 × IN: trips in approximately 3 seconds
- 1.35 × IN: trips in approximately 0.5 seconds
- 2.00 × IN: trips in approximately 0.1 seconds
- 2.50 × IN: trips in approximately 0.012 seconds
Short Circuit Trip Time (IKS) Typically 0.002 seconds
Leakage Current in OFF Condition Typically less than 1 mA
Ambient Temperature Range -25°C to +60°C (operating); -30°C to +70°C (storage)
Dimensions (H x W x D) 12.5 mm x 80 mm x 98.5 mm
Mounting DIN rail EN 60715-35x7.5
Approvals UL 508 Listed, UL 2367 Recognized
N/A
ALLEN BRADLEY

1694-PMD222 | ALLEN BRADLEY | Protection Module, 2 Channels, Fixed Current, 2A, 2A

₹ 4,662.38
Specification Details
Operating Voltage (UB) 24V DC (minimum 18V, maximum 30V)
Rated Current (IN) 2 A per channel
Number of Channels 2
Voltage Drop at IN Typically 180 mV per channel
Overload Disconnection (IOL) - 1.05 × IN: trips in approximately 3 seconds
- 1.35 × IN: trips in approximately 0.5 seconds
- 2.00 × IN: trips in approximately 0.1 seconds
- 2.50 × IN: trips in approximately 0.012 seconds
Short Circuit Trip Time (IKS) Typically 0.002 seconds
Leakage Current in OFF Condition Typically less than 1 mA
Ambient Temperature Range -25°C to +60°C (operating); -30°C to +70°C (storage)
Dimensions (H x W x D) 12.5 mm x 80 mm x 98.5 mm
Mounting DIN rail EN 60715-35x7.5
Approvals UL 508 Listed, UL 2367 Recognized