30 Days Return Policy. Learn more

Click here to contact us.

SPARECRUX is NOT an authorized distributor for BECKHOFF

EL3356 | BECKHOFF | EtherCAT Terminal, 1-channel Analog input, Measuring Bridge, Full Bridge, 16 Bit

₹ 23,750.00

Warranty

We provide a 1-year warranty from the date of purchase for new products. Additionally, surplus / used items come with a 30-day warranty.

Delivery and Shipping

We aim to process orders within 5-7 business days. Shipping options vary by location with tracking provided; international shipping available with customs duties responsibility on customers.


Enquire Now
Interested in this product? Submit your enquiry by entering your details.

Manufacturer Part Number (MPN)

EL3356

Original Equipment Manufacturer

BECKHOFF

Description

Number of inputs 2, for 1 resistor bridge in full bridge technology
Power supply via the E-bus
Distributed clocks
Measuring range UD max. ±27 mV
Measuring range UREF max. ±13.8 V
Internal resistance > 200 kΩ (UREF), > 1 MΩ (UD)
Supported nominal sensitivity all, parameter resolution: 0.01 µV/V; recommended: 0.5…4 mV/V
Input filter limit frequency 10 kHz low pass (-3 dB)
Conversion rate 100…4 samples/s (10…250 ms conversion time)
Power supply UV up to 12 V DC from power contacts, dependent on sensor
Resolution 16 bit, 32 bit presentation
Measurement error/uncertainty < ±0.01% for the calculated load value in relation to the final load value with a 12 V feed and 24 mV bridge voltage (hence nominal strain gauge characteristic value of 2 mV/V), self-calibration active, 50 Hz filter active
Current consumption E-bus typ. 210 mA
Current consumption power contacts depends on strain gauge supply, min. 1 mA
Special features self-calibration, quadruple averager, dynamic filters
Weight approx. 60 g
BECKHOFF

EL3356 | BECKHOFF | EtherCAT Terminal, 1-channel Analog input, Measuring Bridge, Full Bridge, 16 Bit

₹ 23,750.00
Number of inputs 2, for 1 resistor bridge in full bridge technology
Power supply via the E-bus
Distributed clocks
Measuring range UD max. ±27 mV
Measuring range UREF max. ±13.8 V
Internal resistance > 200 kΩ (UREF), > 1 MΩ (UD)
Supported nominal sensitivity all, parameter resolution: 0.01 µV/V; recommended: 0.5…4 mV/V
Input filter limit frequency 10 kHz low pass (-3 dB)
Conversion rate 100…4 samples/s (10…250 ms conversion time)
Power supply UV up to 12 V DC from power contacts, dependent on sensor
Resolution 16 bit, 32 bit presentation
Measurement error/uncertainty < ±0.01% for the calculated load value in relation to the final load value with a 12 V feed and 24 mV bridge voltage (hence nominal strain gauge characteristic value of 2 mV/V), self-calibration active, 50 Hz filter active
Current consumption E-bus typ. 210 mA
Current consumption power contacts depends on strain gauge supply, min. 1 mA
Special features self-calibration, quadruple averager, dynamic filters
Weight approx. 60 g