Description

Number of inputs 1
Power supply 24 V DC via power contacts
Signal current 4…20 mA
Technology single-ended
Internal resistance 80 Ω + diode voltage 0.7 V
Common-mode voltage UCM
Conversion time ~ 1 ms
Resolution 12 bit
Measurement error/uncertainty < ±0.3% (relative to full scale value)
Surge voltage resistance max. 35 V
Electrical isolation 500 V (K-bus/signal voltage)
Current consumption power contacts load only
Current consumption K-bus typ. 65 mA
Bit width in the process image input: 1 x 16 bit data (1 x 8 bit control/status optional)
Configuration no address or configuration setting
Special features with sensor supply
BECKHOFF

KL-3051 | BECKHOFF | Bus Terminal, 1-channel Analog Input, Current, 4…20 mA, 12 Bit, Single-ended

₹ 8,640.00
Number of inputs 1
Power supply 24 V DC via power contacts
Signal current 4…20 mA
Technology single-ended
Internal resistance 80 Ω + diode voltage 0.7 V
Common-mode voltage UCM
Conversion time ~ 1 ms
Resolution 12 bit
Measurement error/uncertainty < ±0.3% (relative to full scale value)
Surge voltage resistance max. 35 V
Electrical isolation 500 V (K-bus/signal voltage)
Current consumption power contacts load only
Current consumption K-bus typ. 65 mA
Bit width in the process image input: 1 x 16 bit data (1 x 8 bit control/status optional)
Configuration no address or configuration setting
Special features with sensor supply